Loading...
04-05-21-Ordinance-Establishing the Building Inspection Department-04/19/2021ORDINANCE # 04-05-21 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF SANGER, TEXAS AMENDING CHAPTER 3 OF THE CODE OF ORDINANCES, ARTICLE 3.100 "BUILDING INSPECTION DEPARTMENT ESTABLISHED", ARTICLE 3.200 'BUILDING CODE", ARTICLE 3.300 "PLUMBING CODE", ARTICLE 3.400 "MECHANICAL CODE", ARTICLE 3.500 "ELECTRICAL CODE", ARTICLE 3.600 "RESIDENTIAL CODE", ARTICLE 3.2200 "REGULATING PLACEMENT OF GAS AND ELECTRIC METERS ON ALL NEW SINGLE FAMILY RESIDENTIAL BUILDINGS", ARTICLE 3.2500 "ENERGY CONSERVATION CODE", ARTICLE 3.2600 "FUEL GAS CODE", ARTICLE 3.2700 "EXISTING BUILDING CODE", ARTICLE 2.900 SWIMMING POOL AND SPA CODE; PROVIDING FOR THE REPEAL OF ALL ORDINANCES IN CONFLICT; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY; AND PROVIDING FOR AN EFFECTIVE DATE. NOW THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF SANGER, TEXAS: Section 1. That Chapter 3 of the Code of Ordinances, City of Sanger, Texas is hereby amended to read as follows: ARTICLE 3.100 BUILDING INSPECTION DEPARTMENT ESTABLISHED (a) There is hereby established a building inspection department to enforce the building codes adopted by the City of Sanger, Texas, to insure and safeguard life and limb, health, property and public welfare. (b) There is hereby established a position of building official to be head of said division, who shall be solely responsible for all matters relative to construction, inspection and enforcement of these codes. The building official of this city shall be appointed by the City Manager or his or her designee, and shall have the powers and duties prescribed for the 'Building Official" by the International Building Code. (c) The building official shall be responsible for the issuance of citations to any person, firm or corporation which is found to be in violation of any building codes or city ordinances, after all other attempts to correct the problem have failed. ARTICLE 3.200 BUILDING CODE See.3.201 Adopted The International Building Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of establishing rules and regulations for the construction, erection, alteration, moving, demolition, repair, use, and occupancy of any building or structure within the city. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. **Sec. 3.202 Amendments "The references in the following sections of the 2018 International Building Code to square feet of fire areas are amended to read "6,000 square feet," to wit: §§903.2.1.1(1), 903.2.1.3(1), 903.2.1.4(1), and 903.2.3(1) **Section 101.4; change to read as follows: 101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.8 and referenced elsewhere in this code, when specifically adopted, shall be considered part of the requirements of this code to the prescribed extent of each such reference. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the Electrical Code shall mean the Electrical Code as adopted. **Section 101.4.7; add the following: 101.4.7 Electrical. The provisions of the Electrical Code shall apply to the installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings and appurtenances thereto. **Section 103 and 103.1 amend to insert the Department Name SECTION 103 BUILDING INSPECTION DEPARTMENT OF THE CITY OF SANGER 103.1 Creation of enforcement agency. The Building Inspection Department of the City of Sanger is hereby created and the official in charge thereof shall be known as the building official. **Section 105.2 Work exempt from permit, under sub -title entitled "Building" delete items 2, and 10 and renumber as follows: Building: 1. (Unchanged) 2. Delete this exemption 3- 2.(Unchanged) 4 3.(Unchanged) 4.(Unchanged) 6 5.(Unchanged) 7. 6.(Unchanged) 8 7.(Unchanged) 8.(Unchanged) 10. Delete this exemption 9.(Unchanged) 10.(Unchanged) 11. (Unchanged) "Section 109; add Section 109.7 to read as follows: 109.7 Re -inspection Fee. A fee as established by city council resolution may be charged when: 1. The inspection called for is not ready when the inspector arrives; 2. No building address or permit card is clearly posted; 3. City approved plans are not on the job site available to the inspector; 4. The building is locked or work otherwise not available for inspection when called; 5. The job site is red -tagged twice for the same item; 6. The original red tag has been removed from the job site. 7. Failure to maintain erosion control, trash control or tree protection. Any re -inspection fees assessed shall be paid before any more inspections are made on that job site. "Section 109, add Section 109.8,109.8.1, 109.8.2 and 109.9 to read as follows: 109.8 Work without a permit. 109.8.1 Investigation. Whenever work for which a permit is required by this code has been commenced without first obtaining a permit, a special investigation shall be made before a permit may be issued for such work. 109.1.2 Fee. An investigation fee, in addition to the permit fee, shall 109.9 Unauthorized cover up fee. Any work concealed without first obtaining the required inspection in violation of Section 110 shall be assessed a fee as established by the city fee schedule. "Section 110.3.5, Lath, gypsum board and gypsum panel product inspection; Delete exception "Section 202; amend definition of Ambulatory Care Facility as follows: AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing or similar care on a less than 24-hour basis to individuals who are rendered incapable of self-preservation by the services provided. This group may include but not be limited to the following: - Dialysis centers - Sedation dentistry - Surgery centers - Colonic centers - Psychiatric centers "Section 202, add definition of Assisting Living Facilities to read as follows. ASSISTED LIVING FACILITIES. A building or part thereof housing persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment which provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff **Section 202; change definition of "Atrium" as follows: ATRIUM. An opening connecting three or more stories... Balance remains unchanged **Section 202; amend definition of "High -Rise Building" to read as follows: HIGH-RISE BUILDING. A building with an occupied floor located more than 55 feet (16764 nun) above the lowest level of fire department vehicle access. **Section 202; amend definition of "Repair Garage" to read as follows: REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement and other such minor repairs. **Section 202; amend definition of "Special Inspector" to read as follows: SPECIAL INSPECTOR. A qualified person employed or retained by an approved agency who shall prove to the satisfaction of the registered design professional in responsible charge and the Building Official as having the competence necessary to inspect a particular type of construction requiring special inspection. **Section 303.1.3; add a sentence to read as follows: 303.1.3 Associated with Group E occupancies. A room or space used for assembly purposes that is associated with a Group E occupancy is not considered a separate occupancy, except when applying the assembly requirements of Chapter 10 and 11. **Section 304.1; add the following to the list of occupancies: Fire stations Police stations with detention facilities for 5 or less **Section 30Z1.1; add the following sentence to Exception 4: 4. Cleaning establishments... (text unchanged) ... with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711 or both. See also IFC Chapter 21, Dry Cleaning Plant provisions. **Section 403.1, Exception 3; change to read as follows: 3. The open-air portions of buildings [remainder unchanged] **Section 403.3, Exception; delete item 2 **Section 403.3.2 change to read as follows: [F] 403.3.2 Water supply to required fire pumps. In buildings that are more than 420 120 feet (36.5 m) in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: {No change to exception.) "Section 404.5, delete Exception. "Section 406.3.5.1; add sentence read as follows: A fire separation is not required between a Group R-2 and U carport provided that the carport is entirely open on all sides and that the distance between the two is at least 10 feet (3048 mm) "Section 506.2; delete the following sentence from table i. The maximum allowable area for a single -story nonsprinklered Group U greenhouse is permitted to be 9000 square feet or the allowable area shall be permitted to comply with Table C102.1 of Appendix C. "Section 506.2.2; add sentence to read as follows: 506.2.2 Open Space Limits. Such open space shall be either on the same lot or dedicated for public use and shall be accessed from a street or approved fire lane. In order to be considered as accessible, if not in direct contact with a street or fire lane, a minimum 10-foot- w i d e pathway meeting fire department access fi•om the street or approved fire lane shall be provided. "Section 506.3.1; add sentence to read as follows: Section 506.3.1 Minimum Percentage of perimeter. [Existing Text to remain] In order to be considered as accessible, if not in direct contact with a street or fire lane, a minimum 10- foot-wide pathway meeting fire department access from the street or approved fire lane shall be provided. "Section 602.1.1; add sentence to read as follows: 602.1.1 Minimum Requirements. [Existing Text to remain] Where a building contains more than one distinct type of construction, the building shall comply with the most restrictive area, height, and stories, for the lesser type construction or be separated by fire walls. "Section 708.4.2; change sentence to read as follows: Exceptions; 1. Buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1, or in accordance with Section 903.3.1.2 provided that sprinkler protection is provided in the space between the top of the fire partition and the underside of the floor or roof sheathing, deck or slab above as required for systems complying with Section 903.3.1.1. Portions of buildings containing concealed spaces filled with noncombustible insulation as permitted for sprinkler omission shall not apply to this exception for draftstopping. [Remainder unchanged] "Section 712.1.9, change item 4 to read as follows: 5. Is not open to a corridor in Group I and H occupancies. "Section 718.3; change sentence to read as follows: 718.3 Draftstopping in floors. [Body of text unchanged] Exceptions: Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and provided that in combustible construction, sprinkler protection is provided in the attic space. **Section 718.4, change sentence to read as follows: 718.4 Draftstopping in attics. [Body of text unchanged] Exceptions: Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and provided that in combustible construction, sprinkler protection is provided in the attic space. **Section 9; refer to: The International Fire Code as amended by City of Sanger. **Section 1006.2.2.7; add a new Section 1006.2.2.7 as follows: 1006.2.2.7 Electrical Rooms. For electrical rooms, special exiting requirements may apply. Reference the electrical code as adopted. **Section]009.8; add the following Exception 7. 1009.8 Two Way Communication. A two-way communication system complying with Sections 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator required to be accessible on each accessible floor that is one or more stories above or below the level of exit discharge. Exceptions: 7. Buildings regulated under State Law and built-in accordance with State registered plans, including variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1009 and chapter 11. **Section 1010.1.9.5 Bolt Locks; amend exceptions 3 and 4 as follows: Exceptions: 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S occupancy. {Remainder unchanged) 4. Where a pair of doors serves a Group A, B, F, M or S occupancy {Remainder unchanged} **Section 10.75.8; amend text as follows: 1. Operable windows where the top of the sill of the opening is located more than 55 feet (16 764 mm) above the finished grade or other surface below and that are provided with window fall prevention devices that comply with ASTM F 2006. **Section 1029.1.1.1 Spaces under grandstands and bleachers; delete this section **Section 1101.1 Scope, Add exception 1101.1 to read as follows: Exception: Components of projects regulated by and registered with Architectural Barriers Division of Texas Department of Licensing and Regulation shall be deemed to be incompliance with the requirements of this chapter. Table 1505.1; delete footnote c and replace footnote b with the following: b. Non -classified roof coverings shall be permitted on buildings of U occupancies having not more than 120 sq. ft. of protected roof area. When exceeding 120 sq. ft. of protected roof area, buildings of U occupancies may use non -rated non-combustible roof coverings. c. [delete] **Section 1505. 7, delete the section **Section 1511.1; add a sentence to read as follows: 1511.1 General. Materials and methods of applications used for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15. All individual replacement shingles or shakes shall be in compliance with the rating required by Table 1505.1. {text of exception unchanged) **Section 1704.2, amend to read as follows: 1704.2 Special inspections and tests. Where application is made to the Building Official for construction as specified in Section 105, the owner or the owner's authorized agent, or the registered design professional in responsible charge, other than the contractor, shall employ one or more approved agencies to provide special inspections and tests during construction on the types of work listed under Section 1705 and identify the approved agencies to the Building Official. The special inspector shall not be employed by the contractor. These special inspections and tests are in addition to the inspections identified by the Building Official that are identified in Section 110. **Section 1704.2.1; amend to read as follows: 1704.2.1 Special inspector qualifications. Prior to the start of construction and or upon request, the approved agencies shall provide written documentation to the registered design professional in responsible charge and the building official demonstrating the competence and relevant experience or training of the special inspectors who will perform the special inspections and tests during construction. [Remainder unchanged] **Section 2901.1; add a sentence to read as follows: [P] 2901.1 Scope. (existing text to remain) The provisions of this Chapter are meant to work in coordination with the provisions of Chapter 4 of the International Plumbing Code. Should any conflicts arise between the two chapters, the Building Official shall determine which provision applies. Table 2902.1; add footnote g to read as follows: g . Drinking fountains are not required in M Occupancies with an occupant load of 100 or less, B Occupancies with an occupant load of 25 or less, and for dining and/or drinking establishments. **Add new Section 2902.1.4 to read as follows: 2902.1.4 Additional fixtures for food preparation facilities. In addition to the fixtures required in this Chapter, all food service facilities shall be provided with additional fixtures set out in this section. 2902.1.4.1 Hand washing lavatory. At least one hand washing lavatory shall be provided for use by employees that is accessible fiom food preparation, food dispensing and ware washing areas. Additional hand washing lavatories may be required based on convenience of use by employees. 2902.1.4.2 Service sink. In new or remodeled food service establishments, at least one service sink or one floor sink shall be provided so that it is conveniently located for the cleaning of mops or similar wet floor cleaning tool and for the disposal of mop water and similar liquid waste. The location of the service sink(s) and/or mop sink(s) shall be approved by the City of Sanger's health department/designee. **Section 3001.2 Emergency Elevator Communication Systems for the deaf, hard of hearing and speech impaired; delete this section **Section 3002.1; Hoistway Enclosure Protection required. Add exceptions to 3002.1 as follows: Exceptions: 1. Elevators completely located within atriums shall not require hoistway enclosure protection. 2. Elevators in open or enclosed parking garages that serve only the parking garage, shall not require hoistway enclosure protection. **Section 3005.4; Machine room, control rooms, machinery spaces and control spaces; delete text as follows: Elevator machine rooms, control rooms, control spaces and machinery spaces outside of but attached to a hoistway that have openings into the hoistway shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Revise text to read: Elevator machine rooms, control rooms, control spaces and machinery spaces shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. **Section 3005.4 Machine rooms, control rooms, machinery spaces and control spaces; Delete exceptions and add two new exceptions to Section 3005.4 as follows: Exceptions. 1. Elevator machine rooms, control rooms, machinery spaces and control spaces completely located within atriums shall not require enclosure protection. 2. Elevator machine rooms, control rooms, machinery spaces, and control spaces in open or enclosed parking garages that serve only the parking garage, shall not require enclosure protection. **Section 3005.7; add a Section 3005.7 as follows: 3005.7 Fire Protection in Machine rooms, control rooms, machinery spaces and control spaces. 3005.7.1 Automatic sprinkler system. The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, except as otherwise permitted by Section 903.3.1.1.1 and as prohibited by Section 3005.7.2.1. 3005.7.2.1 Prohibited locations. Automatic sprinklers shall not be installed in machine rooms, elevator machinery spaces, control rooms, control spaces and elevator hoist -ways. 3005.7.2.2 Sprinkler system monitoring. The sprinkler system shall have a sprinkler control valve supervisory switch and water -flow initiating device provided for each floor that is monitored by the building's fire alarm system. 3005.7.3 Water protection. An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system outside the elevator lobby shall be provided. 3005.7.4 Shunt trip. Means for elevator shutdown in accordance with Section 3005.5 shall not be installed. "Section 3005.8, add Section 3005.8 as follows: 3005.8 Storage _Storage shall not be allowed within the elevator machine room, control room, machinery spaces and or control spaces. Provide approved signage at each entry to the above listed locations stating: "No Storage Allowed. "Section 3006.2; amend text as follows: 5. The building is a high rise and the elevator hoistway is more than 55 feet (16 764 min) in height. The height of the hoistway shall be measured from the lowest floor at or above grade to the highest floors served by the hoistway. Option B Section 3006.2, Hoistway opening protection required; Revise text as follows: 5. The building is a high rise and the elevator hoistway is more than 55 feet (16 764 mm.) in height. The height of the hoistway shall be measured from the lowest floor at or above at grade to the highest floors served by the hoistway. ARTICLE 3.300 PLUMBING CODE See.3.301 Adopted The International Plumbing Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of providing minimum requirements and standards for the protection of the public's health, safety and welfare. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. Sec.3.302 Amendments "Table of Contents, Chapter 7, Section 714; change to read as follows: 714 Engineered Drainage Design ................... 69 "Section 102.8; change to read as follows: 102.8 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 15 and such codes, when specifically adopted, and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference. Where the differences occur between provisions of this code and the referenced standards, the provisions of this code shall be the minimum requirements. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments. Any reference to NFPA 70 or the National Electrical Code shall mean the Electrical Code as adopted. "Sections 106.6.2 and 106. 6.3; change to read as follows: 106.6.2 Fee schedule. The fees for all plumbing work shall be as adopted by resolution of the governing body of the jurisdiction. 106.6.3 Fee Refunds. The code official shall establish a policy for authorizing the refunding of fees {Delete balance of section} "Section 109; Delete entire section and insert the following: Section 109 MEANS OF APPEAL 109.1 Application for appeal. Any person shall have the right to appeal a decision of the code official to the board of appeals established by ordinance. The board shall be governed by the enabling ordinance. "Section 305, change to read as follows: 305.1 Protection against contact. Metallic piping, except for cast iron, ductile iron and galvanized steel, shall not be placed in direct contact with steel framing members, concrete or cinder walls and floors or other masonry. Metallic piping shall not be placed in direct contact with corrosive soil. Where sheathing is used to prevent direct contact, the sheathing shall have a thickness of not less than 0.008 inch (8 ml) (0.203 mm) and the sheathing shall be made of approved material plastic. Where sheathing protects piping that penetrates concrete or masonry walls or floors, the sheathing shall be installed in a manner that allows movement of the piping within the sheathing. 305.4.1 Sewer depth. Building sewers shall be a minimum of 12 inches 304 mm) below grade. "Section 305.7; change to read as follows: 305.7 Protection of components of plumbing system. Components of a plumbing system installed within 3 feet along alleyways, driveways, parking garages or other locations in a manner in which they could be exposed to damage shall be recessed into the wall or otherwise protected in an approved manner. "Section314.2.1; change to read as follows: 314.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal.... {text unchanged} ... Condensate shall not discharge into a street, alley, sidewalk, rooftop, or other areas so as to cause a nuisance. **Section 314.2.2; delete material CPVC **Section413.4; change to read as follows: 412.4 Required location for floor drains. Floor drains shall be installed in the following areas. 1. In public coin -operated laundries and in the central washing facilities of multiple family dwellings, the rooms containing automatic clothes washers shall be provided with floor drains located to readily drain the entire floor area. Such drains shall have a minimum outlet of not less than 3 inches (76 mm) in diameter. 2. Commercial kitchens. In lieu of floor drains in commercial kitchens, the code official may accept floor sinks. 3. Public restrooms. **Section 502.3; change to read as follows: 502.3 Water heaters installed in attics. Attics containing a water heater shall be provided ... {bulk of paragraph unchanged) ... side of the water heater. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), where such dimensions are large enough to allow removal of the water heater. As a minimum, for access to the attic space, provide one of the following: 1. A permanent stair. 2. A pull down stair with a minimum 300 lb (136 kg) capacity. 3. An access door from an upper floor level. 4. Access Panel may be used in lieu of items 1, 2, and 3 with prior approval of the Code Official due to building conditions. Exceptions: 1. The passageway and level service space are not required where the appliance is capable of being serviced and removed... {remainder of section unchanged} **Section 502.6, Add Section 502.6 to read as follows: 502.6 Water heaters above ground or floor. When the attic, roof, mezzanine or platform in which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level, it shall be made accessible by a stairway or permanent ladder fastened to the building. Exception: A max 10 gallon water heater (or larger with approval) is capable of being accessed through a lay -in ceiling and a water heater is installed is not more than ten (10) feet (3048 mm) above the ground or floor level and may be reached with a portable ladder. 502.6.1 Illumination and convenience outlet. Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtainable from the main level, lighting and a receptacle outlet shall be provided in accordance with Section 502.1. **Section 504.6; change to read as follows: 504.6 Requirements for discharge piping. The discharge piping serving a pressure relief valve, temperature relief valve or combination thereof shall: 1. Not be directly connected to the drainage system. 2. Discharge through an air gap. 3. Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air gap. 4. Serve a single relief device and shall not connect to piping serving any other relief device or equipment. Exception: Multiple relief devices may be installed to a single T & P discharge piping system when approved by the administrative authority and permitted by the manufactures installation instructions and installed with those instructions. 5. Discharge to an approved location or to the outdoors. 6. Discharge in a manner that does not cause personal injury or structural damage. 7. Discharge to a termination point that is readily observable by the building occupants. 8. Not be trapped. 9. Be installed so as to flow by gravity. 10. Not terminate less than 6 inches above and not less than two times the discharge pipe diameter above the floor or flood level rim of the wall receptor. 11. Not have a threaded connection at the end of such piping. 12. Not have valves or tee fittings. 13. Be constructed of those materials listed in Section 605.4 or materials tested, rated and approved for such use in accordance with ASME A112.4.1. 14. Be one nominal size larger than the size of the relief valve outlet, where the relief valve discharge piping is installed with insert fittings. The outlet end of such tubing shall be fastened in place. "Section 504. 7.I; amend to read as follows: 504.7.1 Pan size and drain to read as follows: The pan shall be not less than 11/2 inches (38 mm) in depth and shall be of sufficient size and shape to receive all dripping or condensate fiom the tank or water heater. The pan shall be drained by an indirect waste pipe having a diameter of not less than 3/4 inch (19 mm). Piping for safety pan drains shall be of those materials listed in Table 605.4. Multiple pan drains may terminate to a single discharge piping system when approved by the administrative authority and permitted by the manufactures installation instructions and installed with those instructions. "Section 504. 7.2; delete sentence Where a pan drain was not previously installed, a pan drain shall not be required for replacement water heater installation. "Section 604.8; add Section 604.8.3 to read as follows: 604.8.3 Thermal expansion control. An expansion tank or approved device shall be installed for the water heater with the addition of a pressure reducing valve or regulator creating a closed system. "Section 608.1; change to read as follows: 608.1 General. A potable water supply system shall be designed, installed and maintained in such a manner so as to prevent contamination from non -potable liquids, solids or gases being introduced into the potable water supply through cross -connections or any other piping connections to the system. Backflow preventer applications shall conform to applicable local regulations, Table 608.1, and as specifically stated in Sections 608.2 through 608.16.10. "Section 608.17.5; amend to read as follows: 608.16.5 Connections to lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric - type vacuum breaker, a pressure -type vacuum breaker, a double-check assembly or a reduced pressure principle backflow preventer. A valve shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principle backflow preventer. "Section 608.18; change to read as follows: 608.17 Protection of individual water supplies. An individual water supply shall be located and constructed so as to be safeguarded against contamination in accordance with applicable local regulations. Installation shall be in accordance with Sections 608.17.1 through 608.17.8. "Section 703.6, Delete "Section 704.5; added to read as follows: 704.5 Single stack fittings. Single stack fittings with internal baffle, PVC schedule 40 or cast iron single stack shall be designed by a registered engineer and comply to a national recognized standard. "Section 705.11.1; amend to read as follows: 705.11.1 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Solvent cement not purple in color and conforming to ASTM D 2564, CSA B 137.3, CSA B 181.2 or CSA B 182.1 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent cement joints shall be permitted above or below ground. Exception: A primer is not required where both of the following conditions apply: 1. The solvent cement used is third -party certified as conforming to ASTM D 2564 2. The solvent cement is used only for joining PVC drain, waste and vent pipe and fittings in non -pressure applications in sizes up to and including 4 inches (102 mm) in diameter "Section 712.5; add Section 712.5 to read as follows: 712.5 Dual Pump System. All sumps shall be automatically discharged and, when in any "public use" occupancy where the sump serves more than 10 fixture units, shall be provided with dual pumps or ejectors arranged to function independently in case of overload or mechanical failure. For storm drainage sumps and pumping systems, see Section 1113. **Section 713, 713.1; change to read as follows: SECTION 713 ENGINEERED DRAINAGE DESIGN 714.1 Design of drainage system. The sizing, design and layout of the drainage system shall be designed by a registered engineer using approved design methods. **Section 803.3; added to read as follows: 803.3 Special waste pipe, fittings, and components. Pipes, fittings, and components receiving or intended to receive the discharge of any fixture into which acid or corrosive chemicals are placed shall be constructed of CPVC, high silicone iron, PP, PVDF, chemical resistant glass, or glazed ceramic materials. **Section 903.1; change to read as follows: 903.1 Roof extension. Open vent pipes that extend through a roof shall be terminated at least six (6) inches (152 mm) above the roof. Where a roof is to be used for assembly or as a promenade, observation deck, sunbathing deck or similar purposes, open vent pipes shall terminate not less than 7 feet (2134 mm) above the roof. **Section 917 Single stack vent system. Delete entire section. **Section 1003.3.9; added to read as follows: 1003.3.9 Sample Well. A 12 inch sample well shall be provided on all grease interceptors or separators. **Section 1106.1; change to read as follows: 1106.1 General. The size of the vertical conductors and leaders, building storm drains, building storm sewers, and any horizontal branches of such drains or sewers shall be based on six (6) inches per hour rainfall rate **Section 1.708.3; change to read as follows: 1108.3 Sizing of secondary drains. Secondary (emergency) roof drain systems shall be sized in accordance with Section 1106. Scuppers shall be sized to prevent the depth of ponding water from exceeding that for which the roof was designed as determined by Section 1101.7. Scuppers shall not have an opening dimension of less than 4 inches (102 mm). The flow through the primary system shall not be considered when sizing the secondary roof drain system. Section 1109; delete this section. Section 1202.1 delete Exception 1 and 2. ARTICLE 3.400 MECHANICAL CODE See.3.401 Adopted The International Mechanical Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of providing minimum requirements and standards to safeguard life or limb, health, property and public welfare. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. Sec.3.402 Amendments **Section 102.8; change to read as follows: 102.8 Referenced codes and standards. The codes and standards referenced herein shall be those that are listed in Chapter 15 and such codes, when specifically adopted and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the adopted amendments. Any reference to NFPA 70 or the National Electrical Code (NEC) shall mean the Electrical Code as adopted. **Section 306.3; change to read as follows: 306.3 Appliances in attics. Attics containing appliances requiring access shall be provided .. . (bulk of paragraph unchanged) ... side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), or larger where such dimensions are not large enough to allow removal of the largest appliance. A walkway to an appliance shall be rated as a floor as approved by the building official. As a minimum, for access to the attic space, provide one of the following: 1. A permanent stair. 2. A pull down stair with a minimum 300 lb (136 kg) capacity. 3. An access door from an upper floor level. 4. Access Panel may be used in lieu of items 1, 2, and 3 with prior approval of the code official due to building conditions. Exceptions: 1. The passageway and level service space are not required where the appliance is capable of being serviced and removed... (remainder of section unchanged) **Section 306.5; change to read as follows: 306.5 Equipment and appliances on roofs or elevated structures. . Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access, a permanent interior or exterior means of access shall be provided. Permanent exterior ladders providing roof access need not extend closer than & 12 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment and appliances' level service space. Such access shall _ _ _ {bullc of section to read the same} ... on roofs having a slope greater than 4 units vertical in 12 units horizontal (33- percent slope).... {bulk of section to read the same). **Section 306.5.1; change to read as follows: 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on roofs having slopes greater than 3 units vertical in 12 units horizontal (25% slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at the appliance. The level platform shall be provided on each side of the appliance to which access is required for service, repair or maintenance. The platforms shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 21-inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. **Section 306, add Section 306.6 and Section 306.6.1 to read as follows: 306.6 Water Heaters Above Ground or floor. When the mezzanine or platform in which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level, it shall be made accessible by a stairway or permanent ladder fastened to the building. Exception: A max 10-gallon water heater (or larger with approval) is capable of being accessed through a lay -in ceiling and a water heater is installed is not more than ten (10) feet (3048 mm) above the ground or floor level and may be reached with a portable ladder, _ 306.6.1 Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtainable from the main level, lighting and a receptacle outlet shall be provided in accordance with Section 306.3.1. **Section 307.2.2; delete material CPVC: **Section 307.2.3; amend item 2 to read as follows: 2. A separate overflow drain line shall be connected to the drain pan provided with the equipment. Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a higher level than the primary drain connection. However, the conspicuous point shall not create a hazard such as dripping over a walking surface or other areas so as to create a nuisance. **Section 403.2.1; add an item 5 to read as follows: 5. Toilet rooms within private dwellings that contain only a water closet, lavatory or combination thereof may be ventilated with an approved mechanical recirculating fan or similar device designed to remove odors from the air. **Section 501.3; add an exception to read as follows: 501.3 Exhaust discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a public nuisance and not less than the distances specified in Section 501.3.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilating system. Air shall not be exhausted into an attic, crawl space, or be directed onto walkways. Exceptions: 1. Whole -house ventilation -type attic fans shall be permitted to discharge into the attic space of dwelling units having private attics. 2. Commercial cooking recirculating systems. 3. Where installed in accordance with the manufacturer's instructions and where mechanical or natural ventilation is otherwise provided in accordance with Chapter 4, listed and labeled domestic ductless range hoods shall not be required to discharge to the outdoors. 4. Toilet room exhaust ducts may terminate in a warehouse or shop area when infiltration of outside air is present **Section 607.5.1; change to read as follows: 607.5.1 Fire Walls. Ducts and air transfer openings permitted in fire walls in accordance with Section 705.11 of the International Building Code shall be protected with listed fire dampers installed in accordance with their listing. For hazardous exhaust systems see Section 510.1-510.9 IMC. ARTICLE 3.500 ELECTRICAL CODE Sec. 3.501 Compliance with National Electrical Code All electrical construction, alteration, replacement, repair and all material and apparatus used in connection with electrical work and the placement and operation of all electrical apparatus in the city shall be in strict compliance with the standards established by the 2017 Edition of the National Electrical Code as published by the National Fire Protection Association, with local amendments is hereby adopted. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. Sec.3.502 Amendments **Article 100; add the following to definitions Engineering Supervision. Supervision by a Qualified State of Texas Licensed Professional Engineer engaged primarily in the design or maintenance of electrical installations. "Article 110.3(D)(1); add to read as follows: 110.3(D)(1); Meter Identification. On commercial sites meter shall be equipped with a brass tag permanently affixed displaying the address that the meter is servicing. "Section 210.8(A)(1); add to read as follows: 210.8(A) (1); Dwelling Units. In bathrooms and kitchens where Ground -Fault -Circuit - Interruption devices are required the reset shall be located in the room served. "Article 505. 7(A) changed to read as follows: 505.7 Special Precaution. Article 505 requires equipment construction and installation that ensures safe performance under conditions of proper use and maintenance. Informational No. 1: It is important that inspection authorities and users exercise more than ordinary care with regard to the installation and maintenance of electrical equipment in hazardous (classified) locations. Informational No. 2: Low ambient conditions require special consideration. Electrical equipment depending on the protection techniques described by 505.8(A) may not be suitable for use at temperatures lower than -20°C (-4°F) unless they are identified for use at lower temperatures. However, at low ambient temperature, flammable concentrations of vapors may not exist in a location classified Class 1, Zones 0,1, or 2 at normal ambient temperature. (A) Implementation of Zone Classification System. Classification of areas, engineering and design, selection of equipment and wiring methods, installation, and inspection shall be performed by a qualified licensed Professional Engineer in the State of Texas. Sec. 3.503 Inspections It shall be unlawful for any person, firm or corporation to hinder the City inspector while he or she is acting in the line of duty. He or she shall be given free and prompt access to all buildings, whether public or private, or to any other place he or she deems necessary to the proper inspection of any electrical wiring or apparatus within the City of Sanger. No electrical apparatus, device or wire which in the opinion of the City inspector might cause a hazard to human life, shall be constructed or maintained, and the City inspector shall have the right, through the authority of the city council, to discontinue electric current supplying the building or place in which such hazard exists until such time as said hazard is removed or remedied to the satisfaction of said electrical inspector. Prior to taking such action, notification of the intent to discontinue the power will be provided to the customer unless deemed an emergency situation that requires immediate action Upon notification by the City inspector, the Sanger Electric Utilities is hereby authorized to immediately cut off, or cause to be cut off, any and all electrical power from any room, building, power line or district when public safety so demands, or for any other reason deemed sufficient by said City inspector. Sec.3.504 Licenses (a) Valid License Required. It shall be unlawful for any person to install electric wiring or apparatus or to make any repairs, alterations, additions, or changes to electric wiring or apparatus used in connection with electric lighting, heating or power unless such person shall have previously obtained a master or journeyman electrician's license. Sec. 3.505 Registration Required Any company, firm, corporation, association or co -partnership wishing to engage in the business of installing, repairing, changing or altering any electrical wiring or apparatus, shall register with the City providing proof of valid state licensing and insurance prior to issuance of a permit. Sec. 3.506 Electrical Work Permits (a) Work Permit Required. It shall be unlawful for any person to install, change, alter or repair any electric wiring or apparatus (except routine repairs such as the replacement of fuses and lamps, and alleviation of short circuits), until after such person has first obtained a permit in writing to do so from the City of Sanger, and upon the approval of such work said permit shall be returned to said City of Sanger. (b) Electrical Permit Fees. Information and fees as set forth in the fee schedule in the appendix of this code shall be required prior to the issuance of any permit required by this section. Sec. 3.507 Minimum Electrical Service Standards (1) A mast type service pole shall be required and shall be of such construction and so supported that it will withstand the strain imposed by the service drop. The meter base must be not less than five feet six inches (4'6"), nor more than seven feet (6) above ground. The droop pigtail shall be a minimum of eighteen inches (18") long. The roof jack should be of rigid conduit not less than twenty-four inches (24"), nor more than thirty-six inches (36") above roof. A support service bracket is required. All outside air conditioners will be required to have a weatherproof nonfused disconnect switch within eyesight on or near the unit. (2) All newly constructed and remodels that involve an electrical meter base update shall have an external ground that can be visually inspected by the city electric department. Ground shall be of continuous copper (Minimum #6 Solid) conductor attached to the meter base and must be inside a metallic conduit (which is attached to the structure) from the meter base to ground level from where it can be buried and attached to the ground rod. Meter base and electrical panel must be grounded independent Sec. 3.508 Concealed Wiring No person, firm or corporation shall conceal, or cause to be concealed, any electric wiring or apparatus, except with the express permission of the City inspector, and the City inspector is hereby authorized to remove, or cause to be removed any material whatsoever which may conceal any electric wiring or apparatus contrary to this section. Upon completion of the inspection of any electric wiring or apparatus designed to be concealed which is found to be in full compliance with the provisions of this section, the City inspector shall post a notice of inspection at the distribution panel and the posting of said notice shall constitute permission to conceal said electric wiring or apparatus. See.3.509 Liability This article shall not in any way be construed to lessen the liability of any person, firm, corporation or association of persons installing, changing, altering or repairing any electrical wiring or apparatus, or causing the same to be done, for damages to anyone injured thereby; nor shall the City of Sanger be held to assume any liability by reason of the inspection authorized therein, pursuant to the provisions hereof. Sec. 3.510 Regulations Concerning Service (a) It is provided that upon completion of inspection by the electrical inspector, in the event he or she determines that any wiring, installing, repair or alteration so done upon the job or work he or she has inspected does not comply in every respect with the provisions of this article, and if the same has not been done by a person holding a master electrician's license, it shall be the duty of the City inspector to notify the Sanger Electric Utilities of the City of Sanger, Texas or the appropriate electrical service provider, of the location of said place, the name of the owner of persons in charge thereof and of the fact said work or said job does not meet with the approval of such City inspector, and upon said written notice being given it shall be unlawful for any person or employee of said Sanger Electric Utilities, Sanger, Texas, or appropriate electrical service provider to connect any portion of said wiring, with an electric power line operated or used by the City of Sanger. (b) It shall be unlawful for any person, firm or corporation to break the seal on any electric meter without first notifying the Sanger Electric Utilities. (c) It is provided that all inspections, installations, repairs and alterations as provided for in this article shall be subject to such further rules and regulations that may be promulgated by the city council of the City of Sanger, Texas, and such office of the city secretary of said city and shall be available for inspection and examination, and all penalties herein provided for shall apply to such rules and regulations so promulgated. ARTICLE 3.600 INTERNATIONAL RESIDENTIAL CODE See.3.601 Adopted The International Residential Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of providing minimum requirements and standards for the protection of the public's health, safety and welfare. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. Sec.3.602 Amendments "Section R102.4; change to read as follows: R102.4 Referenced codes and standards. The codes, when specifically adopted, and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections R102.4.1 and R102.4.2. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference made to NFPA 70 or the Electrical Code shall mean the Electrical Code as adopted. "Section R105.2; make changes to this section as follows: R105.2 Work Exempt from permits. No changes in first paragraph Building: 1. ...provided the floor area does not exceed 120 square feet... 2. Delete this exemption 3. No changes 4. No changes 5. No changes 6. No changes 7. No changes 8. No changes 9. No changes 10. Decks not exceeding 120 square feet in area... "Section R108.7; Add section below R108.7 Re -inspection fee. A fee as established by city council resolution may be charged when: 1. The inspection called for is not ready when the inspector arrives; 2. No building address or pelmit card is clearly posted; 3. Approved plans are not on the job site available to the inspector; 4. The building is locked or work otherwise not available for inspection when called; 5. The job site is red -tagged twice for the same item; 6. The original red tag has been removed from the job or site and/or, 7. Violations exist on the property including failure to maintain erosion control or trash control. 8. Any re -inspection fees assessed shall be paid before any more inspections are made on that job site. "Section RI10 (RII0.1 through R110.5); delete this section "Section R202; amend definition of "Townhouse" to read as follows: TOWNHOUSE. A single-family dwelling unit constructed in a group of three or more attached units separated by property lines in which each unit extends from foundation to roof and with a yard or public way on at least two sides. Table R301.2(1); fill in as follows: GROUND WIND DESIGN SEISMIC SUBJECT TO wSNOW 0 Z LOAD DESIGN DAMAGE FROM w CATEGORY' W Z Q W � _ Q SPEEDd a c c Weathering a Frost Termite° W 0 4. Z m w 2 0 O Q ty tL X Z a Z (MPH) m Y (U o fo A Line s w w S I- w } Z Q V n Q p _J a LL X Q z W Z W 2 Q F- rn m o a Mn Depthb 5lb/ft n aei aa)i 'cn c °w )tY se Moderate s very 220 F No Local 150 64.90 g115 ust)/ 763 No No No Heavy Code F fastest mile Delete remainder of table Manual J Design Criteria and foot note N "Section R302.1; add exception #6 to read as follows: Exceptions: {previous exceptions unchanged} 6. Open non-combustible carport structures may be constructed when also approved within adopted ordinances. "Section R302.3; add Exception #3 to read as follows: Exceptions: 1. {existing text unchanged} 2. {existing text unchanged} 3. Two-family dwelling units that are also divided by a property line through the structure shall be separated as required for townhouses. "Section R302.5.1; change to read as follows: R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 13/8 inches (35 mm) in thickness, solid or honeycomb core steel doors not less than 13/8 inches (35 mm) thick, or 20-minute fire -rated door "Section R313 Automatic Fire Sprinkler Systems. Delete entire section "Section R315.2.2 Alterations, repairs and additions. Amend to read as follows: Exception: 1. {existing text unchanged) 2. Installation, alteration or repairs of electrical powered {remaining text unchanged) "Section R322 Flood Resistant Construction. Delete section "Section R401.2, amended by adding a new paragraph following the existing paragraph to read as follows. Section R401.2. Requirements. {existing text unchanged} ... Every foundation and/or footing, or any size addition to an existing post -tension foundation, regulated by this code shall be designed and sealed by a Texas -registered engineer Section R401.2.1 Engineered design. Every foundation and/or footing which exceeds 400 square feet in area, or any addition to an existing post tensioned foundation, regulated by this code shall be designed and sealed by a Texas -registered engineer. "Section 602. 6.1; amend the following: R602.6.1 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load -bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 Ga) and 5 inches (127 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148-inch diameter) having a minimum length of 1 1/2 inches (38 mm) at each side or equivalent. Fasteners will be offset to prevent splitting of the top plate material. The metal tie must extend a minimum of 6 inches past the opening. See figure R602.6.1. {remainder unchanged) Figure R602.6.1; delete the figure and insert the following figure: I AND 5IN. WIDE WED ACROSS AND 'EACH SIDE OF THE dNAILS EACH SIDE TOP **Add Section R703.8.4.1.2; Veneer Ties for Wall Studs; to read as follows: R703.8.4.1.2 Veneer Ties for Wall Studs. In stud framed exterior walls, all ties may be anchored to studs as follows: 1. When studs are 16 in (407 mm) o.c., stud ties shall be spaced no further apart than 24 in (737 mm) vertically starting approximately 12 in (381 mm) from the foundation; or 2. When studs are 24 in (610 mm) o.c., stud ties shall be spaced no further apart than 16 in (483 mm) vertically starting approximately 8 in (254 mm) from the foundation. **Section R902.1; Amend and add exception #5 to read as follows: R902.1 Roofing covering materials. Roofs shall be covered with materials as set forth in Sections R904 and R905. Class A, B, or C roofing shall be installed. {remainder unchanged} Exceptions: 1. {text unchanged) 2. {text unchanged) 3. {text unchanged} 4. {text unchanged} 5. Non -classified roof coverings shall be permitted on one-story detached accessory structures used as tool and storage sheds, playhouses and similar uses, provided the floor area does not exceed 120 sq. ft. **Chapter 11 [RE] —Energy Efficiency is deleted in its entirety; Reference the 2018IECCfor energy code provisions as adopted and amended. **Section M1305.1.3; change to read as follows: M1305.1.2 Appliances in attics. Attics containing appliances shall be provided ... {bulk of paragraph unchanged} ... side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. As a minimum, for access to the attic space, provide one of the following: 1. A permanent stair. 2. A pull down stair with a miniinuin 300 lb (136 kg) capacity. 3. An access door fi•om an upper floor level. Exceptions: 1. The passageway and level service space are not required where the appliance can be serviced and removed through the required opening. 2. Where the passageway is unobstructed ... {remaining text unchanged} (Add the following) Water heaters other than tankless shall not be installed within attics; with the exception of replacement of existing water heaters. **Section M1411.3; change to read as follows: M1411.3 Condensate disposal. Condensate from all cooling coils or evaporators shall be conveyed from the drain pan outlet to a sanitary sewer through a trap, by means of a direct or indirect drain. {remaining text unchanged} **Section M1411.3. 1, Items 3 and 4, add text to read as follows: M1411.3.1 Auxiliary and secondary drain systems. {bulk of paragraph unchanged) 1. [text unchanged] 2. [text unchanged] 3. An auxiliary drain pan... [bulk of text unchanged] ... with Item 1 of this section. A water level detection device may be installed only with prior approval of the building official. 4. A water level detection device... [bulk of text unchanged] ... overflow rim of such pan. A water level detection device may be installed only with prior approval of the building official. **Section M1411.3.1.1; add text to read as follows: M1411.3.1.1 Water -level monitoring devices. On down -flow units ... {bulk of text unchanged} ... installed in the drain line. A water level detection device may be installed only with prior approval of the building official. **M1503.6 Makeup Air Required, Amend and add exception as follows: M1503.6 Makeup air required. Exhaust hood systems capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be provided with makeup air at a rate approximately equal to the difference between the exhaust air rate and 400 cubic feet per minute. Such makeup air systems shall be equipped with a means of closure and shall be automatically controlled to start and operate simultaneously with the exhaust system. Exception: Where all appliances in the house are of sealed combustion, power -vent, unvented, or electric, the exhaust hood system shall be permitted to exhaust up to 600 cubic feet per minute (0.28 m3/s) without providing makeup air. Exhaust hood systems capable of exhausting in excess of 600 cubic feet per minute (0.28 m3/s) shall be provided with a makeup air at a rate approximately equal to the difference between the exhaust air rate and 600 cubic feet per minute. **Section M2005.2; change to read as follows: M2005.2 Prohibited locations. Fuel -fired water heaters shall not be installed in a room used as a storage closet. Water heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion air will not be taken from the living space. Access to such enclosure may be from the bedroom or bathroom when through a solid door, weather-stripped in accordance with the exterior door air leakage requirements of the International Energy Conservation Code and equipped with an approved self -closing device. Installation of direct -vent water heaters within an enclosure is not required **Section M2005.2.2; add to read as follows: M2005.2.2 Water heaters other than tanldess shall not be installed within attics; with the exception of replacement of existing water heaters. **Section G2408.3 (305.5); delete. "Section G2415.2.1 (404.2.1); add a second paragraph to read as follows: Both ends of each section of medium pressure gas piping shall identify its operating gas pressure with an approved tag. The tags are to be composed of aluminum or stainless steel and the following wording shall be stamped into the tag: "WARNING: 1/2 to 5 psi gas pressure - Do Not Remove" **Section G2415.2.2 (404.2.2); add an exception to read as follows: Exception: Corrugated stainless steel tubing (CSST) shall be a minimum of 1/2" (18 EDH). **Section G2415.12 (404.12); change to read as follows: G2415.12 (404.12) Minimum burial depth. Underground piping systems shall be installed a minimum depth of 18 inches (457 mm) below grade. G2415.12.1 (404.12.1) Individual Outdoor Appliances; Delete in its entirety **Section G2417.1 (406.1); change to read as follows: G2417.1 (406.1) General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication, and installation practices comply with the requirements of this code. The permit holder shall make the applicable tests prescribed in Sections 2417.1.1 through 2417.1.5 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the building official when the piping system is ready for testing. The equipment, material, power and labor necessary for the inspections and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests. "Section G2417.4; change to read as follows: G2417.4 (406.4) Test pressure measurement. Test pressure shall be measured with a manometer or with a pressure -measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. "Section G24-7 Z 4.1; change to read as follows: G2417.4.1(406.4.1) Test pressure. The test pressure to be used shall be no less than 3 psig (20 kPa gauge), or at the discretion of the Code Official, the piping and valves may be tested at a pressure of at least six (6) inches (152 min) of mercury, measured with a manometer or slope gauge. For tests requiring a pressure of 3 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one half inches (3 1/2"), a set hand, 1/10 pound incrementation and pressure range not to exceed 6 psi for tests requiring a pressure of 3 psig. For tests requiring a pressure of 10 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one-half inches (3 1/2"), a set hand, a minimum of 2/10 pound incrementation and a pressure range not to exceed 20 psi. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa) (1 /2 psi) and less than 200 inches of water column pressure (52.2 kPa) (7.5 psi), the test pressure shall not be less than ten (10) pounds per square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-half times the proposed maximum working pressure. Diaphragm gauges used for testing must display a current calibration and be in good working condition. The appropriate test must be applied to the diaphragm gauge used for testing "Section G2417.4.2; change to read as follows: G2417.4.2 (406.4.2) Test duration. The test duration shall be held for a length of time satisfactory to the Building Official, but in no case for less than fifteen (15) minutes. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 10a), the test duration shall be held for a length of time satisfactory to the Building Official, but in no case for less than thirty (30) minutes. "Section G2420.1 (406.1); add Section G2420.1.4 to read as follows: G2420.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termination fitting, or equivalent support, suitable for the size of the valves, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12-inches from the center of the valve. Supports shall be installed so as not to interfere with the free expansion and contraction of the system's piping, fittings, and valves between anchors. All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting piping. "Section G2420.5.1 (409.5.1); add text to read as follows: G2420.5.1 (409.5.1) Located within the same room. The shutoff valve ... (bulk of paragraph unchanged} ... in accordance with the appliance manufacturer's instructions. A secondary shutoff valve must be installed within 3 feet (914 mm) of the firebox if appliance shutoff is located in the firebox. **Section G2421.1 (410.1); add text and Exception to read as follows: G2421.1 (410.1) Pressure regulators. A line pressure regulator shall be ... {bulk of paragraph unchanged} ... approved for outdoor installation. Access to regulators shall comply with the requirements for access to appliances as specified in Section M1305. Exception: A passageway or level service space is not required when the regulator is capable of being serviced and removed through the required attic opening. **Section G2422.1.2.3 (411.1.3.3) Prohibited locations and penetrations; delete Exception 1 and Exception 4. **Section G2445.2 (621.2); add Exception to read as follows: G2445.2 (621.2) Prohibited use. One or more unvented room heaters shall not be used as the sole source of comfort heating in a dwelling unit. Exception: Existing approved unvented room heaters may continue to be used in dwelling units, in accordance with the code provisions in effect when installed, when approved by the Building Official unless an unsafe condition is determined to exist as described in International Fuel Gas Code Section 108.7 of the Fuel Gas Code. **Section G2448.1.1 (624.1.1); change to read as follows: G2448.1.1 (624.1.1) Installation requirements. The requirements for water heaters relative to access, sizing, relief valves, drain pans and scald protection shall be in accordance with this code. **Section P2603; add to read as follows: P2603.3 Protection against corrosion. Metallic piping, except for cast iron, ductile iron and galvanized steel, shall not be placed in direct contact with steel framing members, concrete or cinder walls and floors or other masonry. Metallic piping shall not be placed in direct contact with corrosive soil. Where sheathing is used to prevent direct contact, the sheathing shall have a thickness of not less than 0.008 inch (8 mil) (0.203 mm) and the sheathing shall be made of approved material. Where sheathing protects piping that penetrates concrete or masonry walls or floors, the sheathing shall be installed in a manner that allows movement of the piping within the sheathing. **Section P2603.5.1 Sewer Depth; change to read as follows: P2603.5.1 Sewer Depth. Building sewers that connect to private sewage disposal systems shall be a minimum of 12 inches (304 mm) below finished grade at the point of septic tank connection. ** Section P2801; change to read as follows: P2801.5.1 Water heaters other than tankless shall not be installed within attics; with the exception of replacement of existing water heaters. P2801.6 Required Pan. Where a storage tank -type water heater or a hot water storage tank is installed in a location where water leakage from the tank will cause damage, the tank shall be installed in a pan constructed of one of the following. 1. Galvanized steel or aluminum of not less than 0.0236 inch (0.6010mm) in thickness, 2. Plastic not less than 0.036 inch (0.9 mm) in thickness. 3. Other approved materials "Section P2801.6.1; change to read as follows: Section P2801.6.1 Pan size and drain. The pan shall be not less than 11/2 inches (38 mm) in depth and shall be of sufficient size and shape to receive all dripping or condensate from the tank or water heater. The pan shall be drained by an indirect waste pipe having a diameter of not less than 3/4 inch (19 mm). Piping for safety pan drains shall be of those materials listed in Table P2905.5. Multiple pan drains may terminate to a single discharge piping system when approved by the administrative authority and permitted by the manufactures installation instructions and installed with those instructions. ** Section P2804.6.1; change to read as follows: Section P2804.6.1 Requirements for discharge piping. The discharge piping serving a pressure relief valve, temperature relief valve or combination thereof shall: 1. Not be directly connected to the drainage system. 2. Discharge through an air gap. Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air gap. 4. Serve a single relief device and shall not connect to piping serving any other relief device or equipment. Exception: Multiple relief devices may be installed to a single T & P discharge piping system when approved by the administrative authority and permitted by the manufactures installation instructions and installed with those instructions. 5. Discharge, to an approved location or to the outdoors. [remainder unchanged] **Section P2902.5.3; change to read as follows: P2902.5.3 Lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric -type vacuum breaker, a pressure -type vacuum breaker, a double-check assembly or a reduced pressure principle backflow preventer. A valve shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principle backflow preventer. **Section P3003.9; change to read as follows: P3003.9.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Solvent cement not purple in color and conforming to ASTM D 2564, CSA B137.3, CSA B181.2 or CSA B182.1 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent cement joints shall be permitted above or below ground. "Section P3111; Combination waste and vent systems, delete this section in its entirety. "Section P3112.2; Vent Collection; delete and replace with the following: P3112.2 Installation. Traps for island sinks and similar equipment shall be roughed in above the floor and may be vented by extending the vent as high as possible, but not less than the drainboard height and then returning it downward and connecting it to the horizontal sink drain immediately downstream from the vertical fixture drain. The return vent shall be connected to the horizontal drain through a wye-branch fitting and shall, in addition, be provided with a foot vent taken off the vertical fixture vent by means of a wye- branch immediately below the floor and extending to the nearest partition and then through the roof to the open air or may be connected to other vents at a point not less than six (6) inches (152 mm) above the flood level rim of the fixtures served. Drainage fittings shall be used on all parts of the vent below the floor level and a minimum slope of one -quarter (1/4) inch per foot (20.9 min/m) back to the drain shall be maintained. The return bend used under the drain -board shall be a one (1) piece fitting or an assembly of a forty-five (45) degree (0.79 radius), a ninety (90) degree (1.6 radius) and a forty-five (45) degree (0.79 radius) elbow in the order named. Pipe sizing shall be as elsewhere required in this Code. The island sink drain, upstream of the return vent, shall serve no other fixtures. An accessible cleanout shall be installed in the vertical portion of the foot vent. "Section E3405.3.1; add to read as follows.: E3405.3.1 Panelboards are prohibited on the exterior of the dwelling unit. ARTICLE 3.2200 REGULATING PLACEMENT OF GAS AND ELECTRIC METERS ON ALL NEW SINGLE-FAMILY RESIDENTIAL BUILDINGS Article 3.2200(b); change to read as follows (b) All newly constructed single-family residential buildings must place electric meters no further than fifteen feet (15') fi•om the front corner of the house and outside of all fences. Article 3.2200(c); change to read as follows (c) All newly constructed single-family residential buildings must place gas meters no further than fifteen feet (15') from the front corner of the house and outside of all fences. ARTICLE 3.2500 ENERGY CONSERVATION CODE See.3.2501 Adopted The International Energy Conservation Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of providing minimum requirements and standards for the protection of the public's health, safety and welfare. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. See.3.2502 Amendments "Section C102IR102 General; add Section C102.1.2 and R102.1.2 to read as follows: C102.1.2 Alternative compliance. A building certified by a national, state, or local accredited energy efficiency program and determined by the Energy Systems Laboratory to be in compliance with the energy efficiency requirements of this section may, at the option of the Code Official, be considered in compliance. The United States Environmental Protection Agency's Energy Star Program certification of energy code equivalency shall be considered in compliance. R102.1.2 Alternative compliance. A building certified by a national, state, or local accredited energy efficiency program and determined by the Energy Systems Laboratory to be in compliance with the energy efficiency requirements of this section may, at the option of the Code Official, be considered in compliance. The United States Environmental Protection Agency's Energy Star Program certification of energy code equivalency shall be considered in compliance. Regardless of the program or the path to compliance, each 1- and 2-family dwelling shall be tested for air and duct leakage as prescribed in Section R402.4.1.2 (N1102.4.1.2) and R403.3.3 (N1103.3.3) respectively. "Section R202 (N1101.6) Definitions; add the following definition: PROJECTION FACTOR. The ratio of the horizontal depth of the overhang, cave or permanently attached shading device, divided by the distance measured vertically from the bottom of the fenestration glazing to the underside of the overhang, cave or permanently attached shading device. "Section R202 (N1101.6) Definitions; add the following definition: DYNAMIC GLAZING. Any fenestration product that has the fully reversible ability to change it performance properties, including U-factor, solar heat gain coefficient (SHGC), or visible transmittance (VT). "Table 402.1.2 (N1102.1.2) INSULATIONAND FENESTRATION REQUIREMENTS BY COMPONENT; the Fenestration U factor for Climate Zone 3 is amended as follows: CLIMATE ZONE FENESTRATION U-FACTOR 3 4.32 0.35 "Table 402.1.4 (N1102.1.4) EQUIVALENT U-FACTORS; the Fenestration U factor for Climate Zone 3 is amended as follows: CLIMATE ZONE FENESTRATION U-FACTOR 3 0-3-2� 0.35 "Section R402.3.2 (N1102.3.2) Glazed fenestration SHGC, amend by adding a paragraph and table following the exception to read as follows: Where vertical fenestration is shaded by an overhang, cave, or permanently attached shading device, the SHGC required in Table R402.1.2 shall be reduced by using the multipliers in Table R402.3.2 SHGC Multipliers for Permanent Projections. TableR402.3.2 SHGC Multipliers for Permanent Projections Projection Factor SHGC :Multiplier (all Other Orientation) SHGC Multiplier (North Oriented) 0-0.10 1.00 1.00 >0.10-0.20 0.91 0.95 >0.20-0.30 0.82 0.91 >0.30-0.40 0.74 0.87 >0.40-0.50 0.67 0.84 >0.50-0.60 0.61 0.81 >0.60-0.70 0.56 0.78 >0.70-0.80 0.51 0.76 >0.80-0.90 0.47 0.75 >0.90-1.00 0.44 0.73 ! North oriented means within 45 degrees of true north. **R402.4.1.2 (NII02.4.1.2) Testing; Add a last paragraph to read as follows: Mandatory testing shall only be performed by individuals that are certified to perform air infiltration testing certified by national or state organizations as approved by the building official. The certified individuals must be an independent third -party entity, and may not be employed; or have any financial interest in the company that constructs the structure. **Section R402.4 (N1102.4) Air leakage (Mandatory); add a new section and table to read as follows: R402.4.1.3 (N1102.4.1.3) Testing option — ACH tradeoff. As an option to the air leakage rate set out in Section R402.4.1.2 (N1102.4.1.2), 1- and 2-family homes meeting all of the listed criteria below and the thermal envelope requirements in Table R402.4.1.3 (N1102.4.1.3) will be considered compliant when tested and verified as having an air leakage rate to not less than or equal to four air changes per hour when tested and reported in accordance with the testing standards and reporting criteria listed in Section R402.4.1.2 (N1102.4.1.2). The compliance equivalency is limited as follows: 1. Limited to a conditioned floor area between 1,000 and 6,000 square feet, 2. Limited to between 2 to 6bedrooms, 3. Assumes all ductwork and mechanical equipment is located in the unconditioned attic, 4. Assumes typical wood framing in the walls and roof, and 5. Assumes one of the following heating/cooling systems: a. All electric system with a heat pump for heating, or b. A system with electric cooling and natural gas heating. Dwellings using electric resistance strip heating do not qualify for this tradeoff. TABLE R402.4.1.3 (N1102.4.1.3) a Envelope Component Option #1 Option #2 R402.4 Air Leakage < 4 ACH50 < 4 ACH50 Wall Insulation R-value R13 + R3b R13 + R3 Fenestration U-factor < 0.32 < 0.32 Fenestration SHGC < 0.25 < 0.25 Ceiling R-value > R49 > R49 Duct Insulation R-value R8 R6 Radiant Barrier Required No Yes u b Except for the values listed in the table, all other mandatory code provisions are applicable. The first value listed is the R-value of cavity insulation, the second value is the R-value of the continuous insulation or insulated siding. 11"(4ji .':!�''- Section R402.4 leakage (Mandatory);/ add /new section/read / / / R402.4.1.4 Testing options for R2 multifamily dwelling units. As an option to the air leakage rate set out in Section R402.4.1.2, multifamily dwelling units will be considered compliant when tested and verified as having an air leakage rate to the air leakage rate set out in either Section R402.4.1.4.1 or Section R402.4.1.4.2 when tested and reported in accordance with the testing standards and reporting criteria listed in Section R402.4.1.2 R402.4.1.4.1 Total air leakage rate for interior multifamily dwelling units. Interior multifamily dwelling units with a measured, "unguarded" total air leakage result of 5.3 ACH50 or less shall be considered compliant. R402.4.1.4.2 Total air leakage rate for corner multifamily dwelling units. Corner multifamily units with a measured, "unguarded" total leakage result of less than 5.0 ACH50 shall be considered compliant. ** Section R402.4 Air leakage (Mandatory); add a new section to read as follows: R402.4.1.5 Sampling options for R2 multifamily dwelling units. For buildings having three or more dwelling units, a minimum of 15% of the dwelling units in each building must be tested as required by Section R402.4.1.2. Prior to beginning sampling for testing, "Initial Testing" is required for each multifamily property. "Initial Testing" shall consist of the 3rd party testing contractor performing the required tests on at least three consecutive dwelling units. Test results fi•om the "Initial Testing" must satisfy minimum code requirements before sampling is permitted. Dwelling units selected for the "Initial Testing" must be within the same building. Dwelling units selected for "Initial Testing" shall not be included in a "sample group" or counted toward the minimum 15% of dwelling units tested. The building official shall randomly select the three dwelling units for "Initial Testing." The building official may delegate the random selection to the designated 3rd party testing contractor. R402.4.1.5.1 Sample group Identification and Sampling. The builder shall identify a "sample group" which may be a building, floor, fire area or portion thereof. All of the dwelling units within the "sample group" must be at the same stage of construction and must be ready for testing. The building official shall randomly select at least 15% of dwelling units from each "sample group" for testing. The building official may delegate the random selection to the designated 3rd party testing contractor. If each tested dwelling unit within a "sample group" meets the minimum code requirements, then all dwelling units in the "sample group" are considered to meet the minimum code requirements. Before a building may be deemed compliant with the testing as required, each "sample group" must be deemed compliant with the minimum code requirements. The sum total of all of the tested dwelling units across all "sample groups" shall not be less than a minimum of 15% of the dwelling units in a building. R402.4.1.5.2 Failure to Meet Code Requirement(s). If any dwelling units within the identified "sample group" fail to meet a code requirement as determined by testing, the builder will be directed to correct the cause(s) of failure, and 30% of the remaining dwelling units in the "sample group" will be randomly selected for testing by the building official, or third -party testing contractor, regarding the specific cause(s) of failure. If any failures occur in the additional dwelling units, all remaining dwelling units in the sample group must be individually tested for code compliance. A multifamily property with three failures within a 90-day period is no longer eligible to use the sampling protocol in that community or project until successfully repeating "Initial Testing." Sampling may be reinstated after at least three consecutive dwelling units are individually verified to meet all code requirements. A Certificate of Occupancy may not may be issued for any building until testing has been performed and deemed to satisfy the minimum code requirements on the dwelling unit(s) identified for testing. R403.3.3 (N1103.3.3) Duct Testing (Mandatory)Add a last paragraph to read. Mandatory testing shall only be performed by individuals that are certified to perform duct testing leakage testing certified by national or state organizations as approved by the building official. The certified individuals must be an independent third -party entity, and may not be employed; or have any financial interest in the company that constructs the structure. ** Section R403.3 Ducts, add a new section to read as follows: R403.3.4.1 Sampling options for R2 multifamily dwelling units. For buildings having three or more dwelling units, a minimum of 15% of the dwelling units in each building must be tested as required by Section R403.3.3. Prior to beginning sampling for testing, "Initial Testing" is required for each multifamily property. "Initial Testing" shall consist of the 3rd party testing contractor performing the required tests on at least three consecutive dwelling units. Test results from the "Initial Testing" must satisfy minimum code requirements before sampling is permitted. Dwelling units selected for the "Initial Testing" must be within the same building. Dwelling units selected for "Initial Testing" shall not be included in a "sample group" or counted toward the minimum 15% of dwelling units tested. The building official shall randomly select the three dwelling units for "Initial Testing." The building official may delegate the random selection to the designated 3rd party testing contractor. R403.3.4.1.1 Sample group Identification and Sampling. The builder shall identify a "sample group" which may be a building, floor, fire area or portion thereof. All of the dwelling units within the "sample group" must be at the same stage of construction and must be ready for testing. The building official shall randomly select at least 15% of dwelling units from each "sample group" for testing. The building official may delegate the random selection to the designated 3rd party testing contractor. If each tested dwelling unit within a "sample group" meets the minimum code requirements, then all dwelling units in the "sample group" are considered to meet the minimum code requirements. Before a building may be deemed compliant with the testing as required, each "sample group" must be deemed compliant with the minimum code requirements. The sum total of all of the tested dwelling units across all "sample groups" shall not be less than a minimum of 15% of the dwelling units in a building. R403.3.4.1.2 Failure to Meet Code Requirement(s). If any dwelling units within the identified "sample group" fail to meet a code requirement as determined by testing, the builder will be directed to correct the cause(s) of failure, and 30% of the remaining dwelling units in the "sample group" will be randomly selected for testing by the building official, or third -party testing contractor, regarding the specific cause(s) of failure. If any failures occur in the additional dwelling units, all remaining dwelling units in the sample group must be individually tested for code compliance. A multifamily property with three failures within a 90-day period is no longer eligible to use the sampling protocol in that community or proj ect until successfully repeating "Initial Testing." Sampling may be reinstated after at least three consecutive dwelling units are individually verified to meet all code requirements. A Certificate of Occupancy may not may be issued for any building until testing has been performed and deemed to satisfy the minimum code requirements on the dwelling unit(s) identified for testing. "Section C402.2.71R402.2 (N1102.2) Specific insulation requirements (Prescriptive); Add Section C402.2.8 and R402.2.14 (NI102.2.14) to read as follows: Section C402.2.8/R402.2.14 (N1102.2.14) Insulation installed in walls. Insulation installed in walls shall be totally enclosed on all sides consisting of framing lumber, gypsum, sheathing, wood structural panel sheathing, netting or other equivalent material approved by the building official. "Section C403.7.4 Energy recovery ventilation systems (Mandatory); add exception #12 to read as follows: 12. Individual ventilation systems that serve an individual dwelling unit or sleeping unit. "Section C403.11.1 Duct and Plenum Insulation and Sealing (Mandatory); is amended by adding a seeond paragraph to read as follows: Environmental ducts and plenums installed in vertical chases, both supply and exhaust, where the ducts or plenums will not be accessible after construction completion, shall be leak tested in accordance with the SMACNA HVAC Air Leakage Test Manual to the installed ductwork class and pressure requirements. Documentation shall be furnished demonstrating that representative sections totaling not less than 25 percent of the duct area have been tested and that all tested sections comply with the requirements of this section. **Section R404.1(N1104.1); revised in its entirety to read as follows: Section R404.1 (N1104.1) Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps. **Section 405.2 (N1105.2); add the exception to read as follows: Section 405.2 (N1105.2) Mandatory requirements. Compliance with the section requires that the mandatory provisions identified in Section 401.2 be met. Supply and return ducts not completely inside the building thermal envelope shall be insulated to an R-value of not less than R-6. Exceptions: 1. For one- and two-family dwellings the maximum envelope leakage of 4 ACH50 is permitted provided the envelope leakage in the Standard Reference Design is 3 ACH50 and all other requirements of Section R405 are met, including all other mandatory measures. The annual energy cost or source energy usage of the Proposed Design must be equal to or less than that of the Standard Reference Design. 2. For multifamily or townhomes and buildings classified as Group R2 and Group R4 of three stories or less the maximum envelope leakage of less than 5 ACH50 is permitted provided the envelope leakage in the Standard Reference Design is 3 ACH50 and all other requirements of Section R405 are met, including all other mandatory measures. The annual energy cost or source energy usage of the Proposed Design must be equal to or less than that of the Standard Reference Design. **Section R405.6.2; add the following sentence to the end of paragraph: Acceptable performance software simulation tools may include, but are not limited to, REM RateTM, Energy Gauge and IC3.Other performance software programs accredited by RESNET BESTEST and having the ability to provide a report as outlined in R405.4.2 may also be deemed acceptable performance simulation programs and may be considered by the building official. **Section C405.9. Voltage drop in feeders; deleted in its entirety. TABLE R406.4 MAXIMUM ENERGY RATING INDEX; amend to read as follows: MAXIMUM ENERGY RATING INDEX CLIMATE ENERGY RATING INDEX 3 65 This table is effective until August 31, 2019. TABLE R406.42 MAXIMUM ENERGY RATING INDEX TABLE R406.43 MAXIMUM ENERGY RATING INDEX CLIMATE ENERGY RATING INDEX 3 59 This table is effective on or after September 1, 2022. "Section C408.3.1 Functional Testing; amend to read as follows: C408.3.1 Functional Testing. Prior to passing final inspection, the registered design professional or approved ggenc shall provide evidence that the lighting control systems have been tested to ensure that control hardware and software are calibrated, adjusted, programmed, and in proper working condition in accordance with the construction documents and manufacturer's instructions. Functional testing shall be in accordance with Sections C408.3.1.1 through C408.3.1.3 for the applicable control type. ARTICLE 3.2600 FUEL GAS CODE Sec.3.2601 Adopted The International Fuel Gas Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of providing minimum requirements and standards for the protection of the public's health, safety and welfare. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. Sec.3.2602 Amendments "Section 102.2; add an exception to read as follows: Exception: Existing dwelling units shall comply with Section 621.2. "Section 102.8; change to read as follows: 102.8 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 8 and such codes, when specifically adopted and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. "Section 306.3; change to read as follows: [M] 306.3 Appliances in attics. Attics containing appliances shall be provided ... {bulk of paragraph unchanged} ... side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 nun), or larger where such dimensions are not large enough to allow removal of the largest appliance. A walkway to an appliance shall berated as a floor as approved by the building official. Asa minimum, for access to the attic space, provide one of the following: 1. A permanent stair. 2. A pull down stair with a minimum 300 lb (136 kg) capacity. 3. An access door from an upper floor level. 4. Access Panel maybe used in lieu of items 1, 2, and 3 with prior approval of the code official due to building conditions. Exceptions: 1. The passageway and level service space are not required where the appliance is capable of being serviced and removed through the required opening. 2. Where the passageway is not less than ... {bulk of section to read the same}. "Section 306.5; change to read as follows: [M] 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet (4877 mm) above grade to access, a permanent interior or exterior means of access shall be provided. Permanent exterior ladders providing roof access need not extend closer than 8 12 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment and appliances' level service space. Such access shall ... {bulk of section to read the same) ... on roofs having a slope greater than 4 units vertical in 12 units horizontal (33-percent slope).... {bulk of section to read the same}. "Section 306.5. 1; change to read as follows: [M] 306.5.1 Sloped roofs. Where appliances, equipment, fans or other components that require service are installed on a roof having a slope of 3 units vertical in 12 units horizontal (25-percent slope) or greater and having an edge more than 30 inches (762 mm) above grade at such edge, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to a level platform at the appliance. The level platform shall be provided on each side of the appliance to which access is required for service, repair or maintenance. The platform shall be not less than 30 inches (762 mm) in any dimension and shall be provided with guards. The guards shall extend not less than 42 inches (1067 mm) above the platform, shall be constructed so as to prevent the passage of a 2 1 -inch-diameter (533 mm) sphere and shall comply with the loading requirements for guards specified in the International Building Code. "Section 306, add Section 306.7 with exception and subsection 306. 7.1 to read as follows: 306.7 Water heaters above ground or floor. When the attic, roof, mezzanine or platform in which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level, it shall be made accessible by a stairway or permanent ladder fastened to the building. "Section 401.5, add a second paragraph to read as follows: Both ends of each section of medium pressure gas piping shall identify its operating gas pressure with an approved tag. The tags are to be composed of aluminum or stainless steel and the following wording shall be stamped into the tag: "WARNING 1/2 to 5 psi gas pressure Do Not Remove" "Section 404.12; change to read as follows: 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 18 inches (458 mm) top of pipe below grade. "Section 404.12.1; Delete in its entirety "Section 406.4; change to read as follows: 406.4 Test pressure measurement. Test pressure shall be measured with a monometer or with a pressure - measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. "Section 406.4.1; change to read as follows: 406.4.1 Test pressure. The test pressure to be used shall be no less than 3 psig (20 kPa gauge), or at the discretion of the Code Official, the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) of mercury, measured with a manometer or slope gauge. For tests requiring a pressure of 3 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one half inches (3 %2"), a set hand, 1/10 pound incrementation and pressure range not to exceed 6 psi for tests requiring a pressure of 3 psig. For tests requiring a pressure of 10 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one-half inches (3 '/2"), a set hand, a minimum of 2/10 pound incrementation and a pressure range not to exceed 20 psi. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa) (1/2 psi) and less than 200 inches of water column pressure (52.2 kPa) (7.5 psi), the test pressure shall not be less than ten (10) pounds per square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-half times the proposed maximum working pressure. Diaphragm gauges used for testing must display a current calibration and be in good working condition. The appropriate test must be applied to the diaphragm gauge used for testing. _ "Section 406.4.2; change to read as follows: 406.4.2 Test duration. Test duration shall be held for a length of time satisfactory to the Code Official, but in no case for less than fifteen (15) minutes. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.481cPa), the test duration shall be held for a length of time satisfactory to the Code Official, but in no case for less than thirty (30) minutes. (Delete remainder of section.) "Section 409.1; add Section 409.1.4 to read as follows: 409.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termination fitting, or equivalent support, suitable for the size of the valves, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12-inches from the center of the valve. Supports shall be installed so as not to interfere with the free expansion and contraction of the system's piping, fittings, and valves between anchors. All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting piping. "Section 410.1; add a second paragraph and exception to read as follows: Access to regulators shall comply with the requirements for access to appliances as specified in Section 306. Exception: A passageway or level service space is not required when the regulator is capable of being serviced and removed through the required attic opening. "Section 621.2; add exception as follows: 621.2 Prohibited use. One or more unvented room heaters shall not be used as the sole source of comfort heating in a dwelling unit. Exception: Existing approved unvented heaters may continue to be used in dwelling units, in accordance with the code provisions in effect when installed, when approved by the Code Official unless an unsafe condition is determined to exist as described in Section 108.7. ARTICLE 3.2700 INTERNATIONAL EXISTING BUILDING CODE See.3.2701 Adopted The International Existing Building Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of providing minimum requirements and standards for the protection of the public's health, safety and welfare. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. See.3.2702 Amendments "Section 102.4, change to read as follows: [A] 102.4 Referenced codes and standards. The codes, when specifically adopted, and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.4.1 and 102.4.2. "Section 202; amend definitions as follows: Existing Building - A building, structure, or space, with an approved final inspection issued under a code edition which is at least 2 published code editions preceding the currently adopted building code; or a change of occupancy. Existing Structure — A building, structure, or space, with an approved final inspection issued under a code edition which is at least 2 published code editions preceding the currently adopted building code; or a change of occupancy. "Section 305.4.2; add Number 7 to the list of requirements as follows: 1. At one accessible family or assisted use toilet room shall be provided in accordance with Chapter 11 of the International Building Code. **Section 406.1; add a code reference to read as follows; Section 406.1 Material. Existing electrical wiring and equipment undergoing repair shall be allowed to be repaired or replaced with like material, in accordance with the requirements of NFPA 70. **Section 504.1.2 Fire Escapes; change to read as follows: 504.1.2 Existing fire escapes. Existing fire escapes shall continue to be accepted as a component in the means of egress in existing buildings only. Existing fire escapes shall be permitted to be repaired or replaced. **Section 504.1.3; delete entire section. **Section 505.3; change to read as follows: 505.3 Replacement window emergency escape and rescue openings. Where windows are required to provide emergency escape and rescue openings in Group R-2 and R-3 occupancies, replacement windows shall be exempt from the requirements of Sections 1030.2, 1030.3 and 1030.5 of the International Building Code provided the replacement window meets the following conditions: (remainder unchanged) **Section 507.1.1 add an exception to read as follows: Exception: Moved historic buildings need not be brought into compliance with the exception of new construction features required as the result of such movement, including but not limited to foundations and/or other structural elements. **Section 507.3 Flood Hazard Areas: delete this section: **Section 702.6, add a code reference to read as follows: 702.6 Materials and methods. All new work shall comply with the materials and methods requirements in the International Building Code, International Energy Conservation Code, International Mechanical Code, National Electrical Code, and International Plumbing Code, as applicable, that specify material standards, detail of installation and connection, joints, penetrations, and continuity of any element, component, or system in the building. **Section 802.5.1; Exception; change to read as follows: 802.5.1 Minimum requirement. Every portion of open -sided walking surface, including mezzanines, equipment platforms, aisles, stairs, ramps and landings that is more than 30 inches (762 mm) above the floor grade and is not provided with guards, or those in which the existing guards are judged to be in danger of collapsing, shall be provided with guards. **Section 803.1; add sentence to read as follows: For the purpose of fire sprinkler protection and fire alarm requirements included in this section, the work area shall be extended to include at least the entire tenant space or spaces bounded by walls capable of resisting the passage of smoke containing the subject work area, and if the work area includes a corridor, hallway, or other exit access, then such corridor, hallway, or other exit access shall be protected in its entirety on that particular floor level. "Section 803.2.4, change Exception to read as follows: Exception: Supervision is not required where the Fire Code does not require such for new construction. "Section 803.3; change section to read as follows: 803.3 Standpipes. Refer to Section 1103.6 of the Fire Code for retroactive standpipe requirements. [Delete rest of Section 804.3.] "Section 805.2; Remove Exception W "Section 805.3.1.2; change to read as follows: 805.3.1.2 Fire Escapes required. For other than Group I-2, where more than one exit is required an existing fire escape complying with section 805.3.1.2.1 shall be accepted as providing one of the required means of egress. "Section 805.3.1.2.1; change to read as follows: 805.3.1.2.1 Fire Escape access and details - ... 1. [Remain unchanged] 2. Access to a fire escape shall be through a door... 3. Item deleted 4. [Remain unchanged] 5. In all building of Group E occupancy up to and including the occupancy, boarding houses, and childcare centers, ladders of escapes used as a required means of egress. "Section 805.5.2 Transoms Add language to read as follows: 805.5.2 Transoms. In all buildings of Group B, E [Remainder unchanged] "Section 904.1; add sentence to read as follows: 12th grade, building of Group I any type are prohibited on fire For the purpose of fire sprinkler protection and fire alarm requirements included in this section, the work area shall be extended to include at least the entire tenant space or spaces bounded by walls containing the subject work area, and if the work area includes a corridor, hallway, or other exit access, then such corridor, hallway, or other exit access shall be protected in its entirety on that particular floor level. "Section 904.1.1; add sentence to read as follows: 904.1.1 High-rise buildings. An automatic sprinkler system shall be provided in work areas of high-rise buildings "Section 1301.3.2; change to read as follows: 1301.3.2 Compliance with other codes. Buildings that are evaluated in accordance with this section shall comply with the International Fire Code. ARTICLE 3.2900 INTERNATIONAL SWIMMING POOL AND SPA CODE The International Swimming Pool and Spa Code, 2018 Edition as published by the International Code Council is hereby adopted for the purpose of providing minimum requirements and standards for the protection of the public's health, safety and welfare. One (1) copy of said code is incorporated herein by reference and shall be kept on file in the office of the building official. Fees are as set forth in the fee schedule in the appendix of this code. Section 2. All ordinances or parts of ordinances in conflict herewith are, to the extent of such conflict, hereby repealed. Section 3. It is hereby declared to be the intention of the City Council that the sections, paragraphs, sentences, clauses, phrases and words of this ordinance are severable and, if any word, phrase, clause, sentence, paragraph, or section of this ordinance shall be declared unconstitutional by the valid judgement or decree of any court competent jurisdiction, such unconstitutionality shall not affect any of the remaining portions of this Ordinance, since the same would have been enacted by the City Council without the incorporation in this ordinance of any such unconstitutional word, phrase, clause, sentence, paragraph or section. Section 4. Any person, filmor corporation who shall violate any of the provisions of this article shall be guilty of a misdemeanor and upon conviction shall be fined in accordance with the general penalty provision found in Section 1.109 of the Code of Ordinances. Section 5. This ordinance will take effect on May 1, 2021. DULY PASSED, APPROVED AND ADOPTED, this theq day of2021, by the City Council of the City of Sanger, Denton County, Texas. APPROVED Thomas E. Muir, MAYOR ATTEST: Chnniz Christy Dyer, DEPUTY CITY SECRETARY DRC MEDIA COMPANY NEWS & ADVERTISING SOLUTIONS One company delivers it all. 3555 Duchess Drive P.O. Box 369 Denton, TX 76202 940-387-381 1 Publication(s): Denton Record -Chronicle PROOF OF PUBLICATION Being duly sworn Whe is the Publisher/authorized designee of Denton Record -Chronicle, in City of Denton/surrounding areas in Denton County; Newspaper of general circulation which has been continuously and regularly published for a period of not less than one year preceding the date of the attached notice, and that the said notice was published in said newspaper Denton Record -Chronicle on the following dates below: 08/10/2021 08/11 /2021 0 (signature of Authorized Designee) Subscribed and sworn to before me this 11th day of August, 2021 by_ (printed name of Designee) Witness my hand and official seal: (suture name of Designee) Notary Public, Denton County, Texas 1PPy p�eG PATRICIA LAGARD Notary Public * State of Texas ID # 13027960-6 9leoF1`�� My Comm. Expires 08-05-2023 SANGER CITY OF P 0 BOX 1729 SANGER TX 76266 Ad Number: 38291 Price: $180.20 ORDINANCE NO.05.10.21 ORDINANCE If 04.05.21 AN ORDINANCE OF THE CITY AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF OF SANGER, TEXAS, SANGER, TEXAS AMENDING AMENDING THE CODE OF THE CODE OF CHAPTER THE ORDINANCES, ARTICLE 10.100 ORDINANCES, 3.100 'SUBDIVISION ORDINANCE' TO , 'BUILDING INSPECTION REVISE FILING FEES AND DEPARTMENT ESTABLISHED', CHARGES REQUIREMENTS; ARTICLE PROVIDING FOR THE REPEAL ARTIC3.200 LE 3.300NG CODE', ARTICLE 3.300 OF ALL ORDINANCES IN 'PLUMBING CODE', ARTICLE CONFLICT; PROVIDING A 3.400 CODE', SEVERABILITY CLAUSE; CAL ARTICLE RiCA ARTICLE PROVIDING FOR A PENALTY; .500'ELEHANICAL ARTICLE CODE', ARTICLE 3.600 AND PROVIDING FOR AN 'RESIDENTIAL CODE', EFFECTIVE DATE. Section 4. ARTICLE 3.2200 'REGULATING Any person, firm or corporation PLACEMENTOF GAS AND violating any of the provisions of ELECTRIC METERS ON ALL this ordinance or the subdivision NEW SINGLE FAMILY regulations adopted hereby shall RESIDENTIAL BUILDINGS', be guilty of a misdemeanor and ARTICLE 3.2500 'ENERGY Upon conviction shall be fined in CONSERVATION CODE', accordance with the general ARTICLE 3.2600'FUEL GAS penalty found in Section CODE', ARTICLE 3.2700 1.109 of the Code of Ordinances. of, EXISTING BUILDING CODE', Section 5. This Ordinance shall ARTICLE 2.900 SWIMMING lake effect on May 4, 2021. DULY POOL AND SPA CODE; PROVIDING FOR THE REPEAL PASSED, APPROVED AND ADOPTED, this 3rd day of May OF ALL ORDINANCES IN 2021. CONFLICT; PROVIDING A SEVERABILITY CLAUSE; ORDINANCE #04.07.21 PROVIDING FOR A PENALTY; AN ORDINANCE OF THE CITY AND PROVIDING FOR AN EFFECTIVE DATE. Section 4. COUNCIL OF THE CITY OF SANGER, TEXAS AMENDING Any person, film or corporation APPENDIX A FEE SCHEDULE who shall violate any of the OF THE CODE OF provisions of this article shall be ORDINANCES, CREATING guilty of a misdemeanor and ARTICLE 9.000'FIRE FEES', upon conviction shall be fined in PROVIDING FOR THE REPEAL accordance with the general OF ALL ORDINANCES IN penalty provision found in Section CONFLICT; PROVIDING A 1.109 of the Code of Ordinances. SEVERABILITY CLAUSE; Section 5. This ordinance will PROVIDING FOR A PENALTY; take effect on May 1, 2021. DULY WAND PROVIDING FOR AN PASSED, APPROVED AND EFFECTIVE DATE. Section 4. ADOPTED, this the 19 day of A film or c oration April 2021. ny person, orp who shall violate any of the provisions of this article shall be guilty of a misdemeanor and upon conviction shall be fined in accordance with the general penalty provision found in Section 1.109 of the Code of Ordinances. Section 5. This ordinance will take effect on May 1, 2021. DULY PASSED, APPROVED AND ADOPTED, this the 19 day of ;April 2021. ORDINANCE # 04.06.21 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF SANGER, TEXAS AMENDING CHAPTER 5 OF THE CODE OF ORDINANCES, ARTICLE 5.200 ,'INTERNATIONAL FIRE CODE'; PROVIDING FOR THE REPEAL OF ALL ORDINANCES IN CONFLICT; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY; AND PROVIDING FOR AN EFFECTIVE DATE. Section 4. Any person, film or corporation who shall violate any of the provisions of this article shall be guilty of a misdemeanor and Upon conviction shall be fined in accordance with the general penalty provision found in Section 1.109 of the Code of Ordinances. DULY PASSED, APPROVED AND ADOPTED, this the 19 day of April 2021. dre 08/10/2021 & 06/11/2021 Ad Copy: ORDINANCE NO. 05-10-21 AN ORDINANCE OF THE CITY OF SANGER, TEXAS, AMENDING THE CODE OF ORDINANCES, ARTICLE 10.100 "SUBDIVISION ORDINANCE" TO REVISE FILING FEES AND CHARGES REQUIREMENTS; PROVIDING FOR THE REPEAL OF ALL ORDINANCES IN CONFLICT; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY; AND PROVIDING FOR AN EFFECTIVE DATE. Section 4. Any person, firm or corporation violating any of the provisions of this ordinance or the subdivision regulations adopted hereby shall be guilty of a misdemeanor and upon conviction shall be fined in accordance with the general penalty provision found in Section 1.109 of the Code of Ordinances. Section 5. This Ordinance shall take effect on May 4, 2021. DULY PASSED, APPROVED AND ADOPTED, this 3rd day of May 2021. ORDINANCE #04-07-21 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF SANGER, TEXAS AMENDING APPENDIX A FEE SCHEDULE OF THE CODE OF ORDINANCES, CREATING ARTICLE 9.000 "FIRE FEES", PROVIDING FOR THE REPEAL OF ALL ORDINANCES IN CONFLICT; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY; AND PROVIDING FOR AN EFFECTIVE DATE. Section 4. Any person, film or corporation who shall violate any of the provisions of this article shall be guilty of a misdemeanor and upon conviction shall be fined in accordance with the general penalty provision found in Section 1.109 of the Code of Ordinances. Section 5. This ordinance will take effect on May 1, 2021. DULY PASSED, APPROVED AND ADOPTED, this the 19 day of April 2021. ORDINANCE # 04-06-21 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF SANGER, TEXAS AMENDING CHAPTER 5 OF THE CODE OF ORDINANCES, ARTICLE 5.200 "INTERNATIONAL FIRE CODE"; PROVIDING FOR THE REPEAL OF ALL ORDINANCES IN CONFLICT; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY; AND PROVIDING FOR AN EFFECTIVE DATE. Section 4. Any person, film or corporation who shall violate any of the provisions of this article shall be guilty of a misdemeanor and upon conviction shall be fined in accordance with the general penalty provision found in Section 1.109 of the Code of Ordinances. DULY PASSED, APPROVED AND ADOPTED, this the 19 day of April 2021. ORDINANCE # 04-05-21 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF SANGER, TEXAS AMENDING CHAPTER 3 OF THE CODE OF ORDINANCES, ARTICLE 3.100 "BUILDING INSPECTION DEPARTMENT ESTABLISHED", ARTICLE 3.200 "BUILDING CODE", ARTICLE 3.300 "PLUMBING CODE", ARTICLE 3.400 "MECHANICAL CODE", ARTICLE 3.500 "ELECTRICAL CODE", ARTICLE 3.600 "RESIDENTIAL CODE", ARTICLE 3.2200 "REGULATING PLACEMENT OF GAS AND ELECTRIC METERS ON ALL NEW SINGLE FAMILY RESIDENTIAL BUILDINGS", ARTICLE 3.2500 "ENERGY CONSERVATION CODE", ARTICLE 3.2600 "FUEL GAS CODE", ARTICLE 3.2700 "EXISTING BUILDING CODE", ARTICLE 2.900 SWIMMING POOL AND SPA CODE; PROVIDING FOR THE REPEAL OF ALL ORDINANCES IN CONFLICT; PROVIDING A SEVERABILITY CLAUSE; PROVIDING FOR A PENALTY; AND PROVIDING FOR AN EFFECTIVE DATE. Section 4. Any person, film or corporation who shall violate any of the provisions of this article shall be guilty of a misdemeanor and upon conviction shall be fined in accordance with the general penalty provision found in Section 1.109 of the Code of Ordinances. Section 5. This ordinance will take effect on May 1, 2021. DULY PASSED, APPROVED AND ADOPTED, this the 19 day of April 2021. dre 08/10/2021 & 08/1 1 /2021